I have a 4 to 20mA output pressure sensor, is there a way of converting the current output into a 10 volt output signal so I can use a voltage input data acquisition card?
Typically a 4-20mA output pressure sensor is configured as 2 wire current loop and with this type of signal circuit it is possible to add load resistance without affecting the current signal. At a particular pressure the pressure sensor behaves like a constant current source regardless of the load resistance connected in series to the circuit. If a 500 Ohm load resistor is added in series to the loop circuit, it is possible to generate a voltage drop across the resistor which will vary from 2 to 10 volts according to the current output variation of 4 to 20mA. So a 2-10Vdc output signal can be sent to the data acquisition card connecting the input wires across the load resistor.
A 4-20mA pressure sensor has a low and high limit of load resistance that must not be exceeded. the limits vary depending on the product type and supply voltage. The resistance limits are normally specified on the product data sheet. This is important to consider since by generating a 2-10Vdc signal you have added an additional 10V max to the circuit which will be deducted for the power supply. Therefore you need to ensure there is sufficient voltage left to power the 4-20mA pressure sensor without exceeding the maximum supply voltage for the circuit.
Featured 4-20ma output pressure sensor products
Differential Pressure Transmitters - Differential pressure transmitters for measuring the DP of fluids and gases across particle filters and along a length of pipe to monitor flow.
HART® Pressure Transmitters - Explore HART pressure transmitters utilizing digital communication over standard 4-20mA wiring for advanced diagnostics, remote configuration, and seamless DCS integration.
Related Help Guides
- Choosing calibrator for pressure transmitters
- Advantages and Disadvantages of using a 4 to 20 mA Signal
- How to create a list of specification parameters for a pressure sensor
- How do you measure flow rate with a dp cell
- Why use 4-20mA and 3-15 psi rather than 0-20mA & 0-15psi
- Supply voltage and load resistance considerations for pressure transmitters
- How to Connect a 4-20mA Current Loop Pressure Transmitter
- Transforming a 2 wire Current Loop into a Voltage Output Signal
- What is the difference between a pressure transducer and a transmitter
Related Technical Terms
- 2 Wire
- 3 Wire
- 4 to 20 mA Current Loop Output Signal
- Amplified Voltage Output
- HART®
- Square Root Extraction
- Stainless Steel Pressure Sensors
- Transmitter
- Turndown Ratio
Related Online Tools
- Pressure Transmitter 4-20mA Current Output Calculator
- Flow Transmitter 4-20mA Current Output Calculator
- DP Flow Transmitter Output Calculator
- 4-20mA Signal to Measurement Reading Converter
- SqRt Extraction 4-20mA Signal to Measurement Reading Converter
- Temperature Transmitter 4-20mA Current Output Calculator
- Liquid Level Transmitter 4-20mA Current Output Calculator
- 0-10V Signal to Measurement Reading Converter
- Pressure Transducer 0-10V Voltage Output Calculator
- 4 to 20 mA Supply, Load, Shunt and Signal Calculator
Related Application Questions and Answers
- 16 bar, 200°C steam pressure transmitter and gauge
- 0-50Vac input to 0-10Vdc output converter
- 4 x 4-20mA Signal Wireless Repeater
- Atmospheric range for 4-20mA pressure sensor
- All-In-One transmitter for measuring steam temperature to 150°C and pressure to 4kg/cm² g
- Vacuum suction sensor & wall mount digital readout with switched contacts
- Stainless steel 316L wetted parts 100 mbar ATEX pressure transmitter
- Industrial dishwasher 0-1m 0-10Vdc water level sensor
- 5 to 20 psi absolute ambient 4 to 20 ma pressure transmitter
- Water temperature depth sensor for cooling tower sump
- Solvent compatible +/-100mWG dp transmitter with PTFE seals
- Vacuum pump inlet to outlet differential pressure sensor with 1500 Torr range
Contact us about this How to get a 10 volt signal from a 4-20mA output pressure sensor page to request more information, or to discuss your application requirements.